Flow Mesurement Knowledge

The presentation of ARTang after-sales case 3

Views:0     Author:Site Editor     Publish Time: 2021-08-26      Origin:Site

Customer's feedbacks about on-sit issues


A certain sewage treatment plant in hefei city Anhui province in china:The data of DN600 meter’s head is shaking electromagnetic flowmeter  The same phenomenon still occurs after the pump is restarted.


Troubleshooting and analysis from technical group of ARTang


Upon receiving feedback from the customer, the Anretang technical team immediately went to the customer site to examine and analyze the faults:

The electromagnetic flowmeter was detected in the field by ARTang engineer and found that the electromagnetic flowmeter was stable at around 800 m3. The resistance value of the electromagnetic flowmeter was normal when use  a multimeter to check. After the pump was restarted again, the dispalys of the screen  was found to fluctuate at the range of 800-2400 m3. Then , ARTang engineer started the other three pumps and found that the flowmeter iwas stable at 2400m3. Determined that the fluctuations was caused by  bubbles in the pipes.


Solution


Install  exhaust valves in the pipeline to exhaust bubbles completely. 


Customer feedbacks


After installation of exhaust valve, the output data of electromagnetic flowmeter head is stable and running well.


What should be done if there are bubbles inside the pipes?


1. If the bubbles inside the measured pipe are caused by the improper installation position of the electromagnetic flowmeter, e.g. the electromagnetic flowmeter is installed at the high point of the pipe (height > 5 m) ,and the residual gas or outside inhaled air will cause the screen signal beat , the measurement error due to the bubble problem can be solved by changing the installation position of the electromagnetic flowmeter, e.g. the electromagnetic flowmeter is installed at the lowest point of the pipeline or install instruments on the U-type pipe.

2. If the calibre of the electromagnetic flowmeter is large or it is not convenient to replace the installation position of the electromagnetic flowmeter, the collection and exhaust valves can be installed upstream of the electromagnetic flowmeter; According to professional research ,a electromagnetic flowmeter with large-calibre can display signal jumps due to bubbles problems, the jumping range is 20%-50%;and the measurement can be restored to normal basically after installing the exhaust valve and the collection package.


ARTANG flowmeter
Phone:
+8618868437258
Email:
luisa@artang.com
Factory:
Hangzhou City, Zhejiang
About ARTang
ARTang is the flow & level measurement manufacturer in China, specialied in electromagnetic flowmeter, liquid analysis, vortex flowmeter, level meter, widely used in water/sewage flow measurement, chemical process flow measurement, food process flow measurement, flow measurement of solid liquid, steam delivery flow measurement.