ACT125 Conductivity Transmitter with High/Low Relay Control

The ARTang ACT125 is a panel-mount conductivity transmitter and controller for water treatment, process-water monitoring and OEM equipment.

It supports conductivity electrodes with cell constants of 0.1, 1.0 and 10.0 cm⁻¹, with measurement ranges up to 200 mS/cm depending on the selected configuration.

Analog Output: 4–20 mA

Control Outputs: High/low-limit relays

Temperature Compensation: Automatic

Power Supply: 24 V DC

    Product Description

    The ACT125 connects to a compatible conductivity electrode to measure water and aqueous process liquids. Operators can check the measurement locally, send it to a PLC through the 4–20 mA output and use the relay outputs for external alarms or control circuits.

    High- and low-limit functions support applications where conductivity must be monitored against upper and lower thresholds.

    The panel-mounted design suits water-treatment skids, control cabinets and equipment panels.

    Technical Specifications

    Parameter

    Specification

    Model

    ACT125

    Product type

    Panel-mount conductivity transmitter and controller

    Measurement Ranges

    See range and electrode table below

    Accuracy

    1.5% FS

    Temperature Compensation

    Automatic

    Process Temperature

    0–100°C, subject to the selected electrode’s rating

    Supported Electrode Cell Constants

    0.1, 1.0 and 10.0 cm⁻

    Display

    3½-digit segment LCD

    Analog Output

    4–20 mA

    Control Outputs

    High/low-limit relays

    Power Supply

    24 V DC

    Ambient Temperature

    0–50°C

    Relative Humidity

    ≤85%

    Housing Dimensions

    96 × 96 × 46 mm (H × W × D)

    Panel Cutout

    92 × 92 mm (H × W)

    Installation

    Panel mount

    Measurement Ranges and Electrode Selection

    Available Measurement Range

    Electrode Cell Constant

    0–20 μS/cm

    0.1 cm⁻

    0–20 μS/cm; 0–200 μS/cm; 0–2,000 μS/cm

    1.0 cm⁻¹

    0–20 mS/cm

    1.0 cm⁻¹

    0–200 mS/cm

    10.0 cm⁻¹

    Product Features and Advantages

    ACT125 conductivity controller with high- and low-limit relay control for conductivity threshold monitoring

    High- and Low-Limit Relay Control

    The ACT125 provides high/low-limit relay outputs for applications requiring conductivity threshold monitoring. This supports equipment designs that need both an upper conductivity warning and a lower conductivity warning.

    4–20 mA Output for PLC Integration

    Automatic Temperature Compensation

    Compact Design for Control Panels

    24 V DC Power and Multiple Electrode Constants

    Typical Applications

    Water Treatment and Reverse Osmosis Systems

    Monitor conductivity at selected feed-water, treated-water or permeate measurement points.

    Rinse-Water Monitoring

    Process and Circulating Water

    Provide local indication and remote monitoring for industrial process-water supplies, circulating-water systems and cooling-water equipment.

    OEM Water-Treatment Equipment

    Integrate conductivity measurement and threshold outputs into water-treatment skids, monitoring panels and liquid-processing equipment.

    Frequently Asked Questions

    What is the difference between the analog and relay outputs?

    The 4–20 mA output represents the measured conductivity for a compatible analog input. The high/low-limit relay outputs provide switching signals for external alarms or control circuits.

    Which conductivity electrodes can be used?

    The ACT125 supports cell constants of 0.1, 1.0 and 10.0 cm⁻¹. The electrode’s temperature element, wiring, measurement range and process compatibility must also match the instrument and application.

    What panel opening is required?

    The panel cutout is 92 × 92 mm. The housing measures 96 × 96 × 46 mm, excluding any additional installation clearance needed for connections and wiring.

    Discuss Your Conductivity Control Requirements

    Send ARTang your expected conductivity range, process liquid, temperature, pressure and alarm requirements. If you already have a sensor, include its model, cell constant and temperature element.

    Our technical team can help review the ACT125 configuration, electrode pairing and system connections for your equipment.

      Factory Strength & Quality Assurance

      ARTang supports industrial measurement projects with in-house production, strict calibration, certified quality control, and global exhibition experience.

      Factory Production

      In-house production and assembly for stable product quality and reliable delivery.

      Worker operating production equipment for instruments and meters

      CNC Machining Equipment

      ARTang worker operating production instruments and equipment

      Product Assembly

      CNC Machining

      Welding Process

      artang warehouse

      warehouse

      Technical Support Department

      Certified Quality

      Product certificates and quality control systems support reliable industrial measurement applications.

      CE certificate for electromagnetic flowmeter

      CE

      ISO 9001 quality management system certificate

      ISO

      3-A sanitary certificate for electromagnetic flowmeter

      3-A

      NEPSI explosion protection certificate for integral magnetic flowmeter

      NEPSI

      Exhibition Experience

      ARTang meets customers and distributors at industry exhibitions to better understand project needs and market requirements.

      ARTang at an industrial instrumentation exhibition, showcasing flow meters and pressure transmitters for process automation applications